[EPCOS POWER FACTOR CORRECTION] |
|
 |
PHASECAP ® AC CAPACITORS - [TECHNICAL DATA] |
|
|
|
|
Standards IEC 831-1/96, IEC 831-2/95, EN 60831-1 +2/96, VDE 560-46+47 3/95. |
|
|
| |
|
|
|
| |
|
|
|
|
|
| Overvoltage |
U max. |
Un + 10 % (Up to 8 h daily) /Un + 15 % (Up to 30 |
| |
|
min daily) / Un + 30 % (up to 1 min) |
|
|
|
| Overcurrent |
I max. |
1.6 * In, in certain cases higher [See Table] |
|
|
|
| Inrush current |
Is |
200 * In |
|
|
|
| Losses (Dieelectric) |
|
< 0.2 W/kvar |
|
|
|
| Capacitence tolernace |
|
+ 5% |
|
|
|
| Test voltage, terminal / terminal |
UTT |
2.15 * Un1, AC, 10 s |
|
|
|
| Test voltage, terminal / case |
UTC |
up to Un < 660 V:300 Vac, 10 s |
| |
|
|
|
|
|
| Useful life |
Tld (co) |
130,000 h |
|
|
|
| Ambient temperature |
LCT/ |
-25% D, max. 55° C, with forced cooling higher |
| |
UCT |
ambient temperature possible: in some cases differ |
| |
|
ent temperature category for 60 Hz [See table]. |
|
|
|
| Cooling |
|
natural or forced. |
|
|
|
| Humidity |
Hrel |
max. 95% |
|
|
|
| Altitude |
|
4000 m asl [above sea level.] |
|
|
|
| Mounting Position |
|
upright. |
|
|
|
| Mounting and Grounding |
|
threaded M 12 stud on bottom of case. |
|
|
|
| Safety |
|
dry technology, overpressure disconnector, self |
| |
|
healing |
|
|
|
| Discharge resistors |
|
discharge module included |
|
|
|
| Case |
|
extruded aluminium |
|
|
|
| Enclosure |
|
IP20, indoor mounting (optionally with lid for IP54) |
|
|
|
| Dielectric |
|
Polypropylene film |
|
|
|
| Impregnation |
|
non-PCB, inert gas |
|
|
|
| Terminals |
|
dual, three-way SIGUT terminal strip with eletric |
| |
|
shock protection (VDE 0106 part 100), max.35 mm² |
| |
|
cable cross-section |
|
|
|
| |
|
|
|
|
|
|
|
| |
 |
PHASECAP ® HD AC CAPACITORS - [HIGH INRUSH CURRENT WITHSTAD CAPABILITY IS CRUCIAL] |
|
|
|
| |
Capacitors used for power factor correction undergo a lot of switching operations. The high |
| |
inrush currents that go along with this must be handled without degrading useful life. The pulse |
| |
strength of this technology comes in particular from the enlarged, sensitive contact area |
| |
(improved metalspraying). The breakthrough came with a Siemens patent called the wavy cut, |
| |
plus heavy edge film design. PhaseCap HO capacitors can easily handle inrush currents of up |
| |
to 200 times rated current. |
| |
|
| |
|
|
|
|
|
|
 |
PHASECAP ® HD AC CAPACITORS - [ AND WHERE IT IS CRUCIAL] |
|
|
|
| |
Parallel connection of capacitors. |
| |
Non-detuned capacitors. |
| |
Capacitor banks using standard contactors. |
| |
Restoration after voltage interruptions and brownouts. |
| |
|
| |
|
|
|
|
|
|
 |
PHASECAP ® HD AC CAPACITORS - [ EXTENDED USEFUL LIFE 130,000 OPERATING HOURS] |
|
|
|
| |
After a long drying phase in a high vacuum to eliminate moisture from the active element, the |
| |
capacitor is impregnated. The case is filled with inert gas and sealed. Then routine test are |
| |
performed for gas leakage. This production process helps to avoid oxidation and partial |
| |
discharges (corona effect), promoting capacitance stability over an extremely long period, an |
| |
essential in filter circuit applications. |
| |
The Compact Phasecap HD capacitor is a self healing. metalized polypropylene film capacitor. |
| |
The current-carrying metal layer (electrode) is vapour-deposited onto one side of film. |
| |
|
|
|
|
|
|
 |
PHASECAP ® HD AC CAPACITORS - [ COMPACT DESIGN - LOW HEIGHT, WEIGHT AND VOLUME] |
|
|
| |
The entire capacitor is composed of three single-phase element stacks. The electrodes are |
| |
connected by metal spraying the face ends of the winding elements. The capacitor elements |
| |
are delta connected. The winding elements are housed in a cylindrical aluminum case and |
| |
hermetically sealed by a press-rolled metal lid. |
| |
|
| |
|
|
|
|
|
|
 |
PHASECAP ® HD AC CAPACITORS - [ TRIPLE SAFETY SYSTEM ] |
|
|
|
| |
Dry technology: - instead of a liquid impregnating agent, the capacitor is filled with gas. So |
| |
there is no risk of fire caused by spurting or leaking oil. Dry design is a must for ecologically |
| |
sensitive applications and insurance follow-up. |
| |
Self-healing:- the capacitor repairs itself after overload. |
| |
Overpressure disconnector: - this prevents the capacitor from bursting at the end of its useful |
| |
life or through electrical or thermal overload. |
| |
|
| |
|
|
|
|
|
|
 |
PHASECAP ® HD AC CAPACITORS - [ INNOVATIVE RELIABLE SIGUP-CONNECTION TECHNOLOGY ] |
|
|
|
| |
SIGUT terminals ensure reliable and straightforward connection, even in a parallel capacitor |
| |
circuit, with benefits like |
| |
Simplified parallel connection of input ends in series. |
| |
Protection against electric shock hazard (IP20 to VDE 0106 part 100). |
| |
Additional connection of discharge resistors for extra reliability and safety. |
| |
Clamping device to prevent loosening of screws. |
| |
Cable cross-sections up to 35 mm². |
| |
|
| |
|
|
|
|
|
|
 |
PHASECAP ® AC CAPACITORS - [OVERPRESSURE DISCONNECTOR] |
|
|
|
| |
 |
| |
| * LP- List Price inclusive of excise duty but exclusive of sales tax or any other taxes. |
|
|
|
|
|
| |
For Improved power quality and reduction in energy costs. |
Top |
 |
|
|